Pressure valuation
Result of compressing load application tests made by TUM Technical University Munich
The demand of the load capacity by a hollow- space- floor are comming up by the expexted surface and point load.
Extract of the compressive load application test of HARBOLA- hollow- space- floor
|
|
ultimate load
AE 20 |
ultimate load
AE 30 |
ultimate load
ZE 20 |
ultimate load
ZE 30 |
| point load |
4 x 4 cm |
17,47 kN |
19,96 kN |
36,47 kN |
51,94 kN |
| stripe load |
6 cm |
not tested |
not tested |
105,80 kN |
120,00 kN |
| stripe load |
10 cm |
not tested |
not tested |
51,59 kN |
69,87 kN |
| surface load |
48,8 x 48,8 cm |
simillar to ZE 20 |
simillar to ZE 30 |
1101,00 kN |
1566,00 kN |
| 1 mug filled |
|
341,30 kN |
429,20 kN |
285,20 kN |
422,20 kN |
ZE = cement screed,
AE = anhydride screed
The load capacity of the HARBOLA hollow- space- floor at final state (covered by screed) is only depending of the compression- and bending tensile strength of the screed and the hight. In testing case= screed hight 5 cm.